Utility Fan Guide: When to Use a Centrifugal Utility Fan

A utility fan (also called a utility set or centrifugal blower) is the fan to choose when an exhaust system has to push air through real resistance: long ducts, many bends, grease filters or an ecology unit. This guide explains how utility fans differ from roof fans, when you need one, and how to choose between the sizes in our CBA utility range. It is written by the AMH-CO team, who have supplied and installed kitchen ventilation and ANSUL fire suppression systems in Saudi Arabia since 2007.

What is a utility fan?

A utility fan is a centrifugal blower with a scroll-shaped housing. Air enters at the side through the inlet and leaves at a right angle through the outlet, which connects directly to the duct. The scroll housing lets the fan build up more pressure than an axial or roof fan of similar size, so it keeps moving air when the system resistance is high.

Our CBA series has a fully welded steel structure with an electrostatically applied, baked powder coating for corrosion resistance. It uses concentric mount bearings, is available in belt drive and direct drive configurations with different motor brackets, and is manufactured under ISO 9001 quality control.

According to the manufacturer’s catalogue, the restaurant-type CBA-TK series is built for large air volume at medium pressure, in carbon steel or stainless steel. The motors are rated IP54 with class F insulation and run on 220 V single-phase or 380 V three-phase, 60 Hz (larger motors are three-phase only). The outlet can be set in eight positions at 45° steps, for clockwise or counter-clockwise rotation, so the fan can match the duct route without extra bends.

When should you choose a utility fan?

  • Kitchens with an ecology unit for smoke and odour control. The filters in the unit add significant resistance, which a utility fan is designed to overcome.
  • Long or complex duct routes, for example when the kitchen is on a lower floor and the duct rises through several levels or has many direction changes.
  • Ground-level or plant-room installation, where the fan cannot sit on the roof at the end of the duct.
  • Other exhaust duties with resistance, such as paint spray booths, chemical storage rooms and laboratory fume exhaust.

Planning an ecology unit? Read our ecology unit guide to size the unit and the fan together.

Utility fan vs upblast roof fan

Utility (CBA)Upblast roof (RCU)
LocationRoof, floor or plant roomOn a roof curb at the end of the duct
Pressure capabilityHigher: suited to filters, ecology units and long ductsLower: suited to short, direct duct runs
DischargeThrough the outlet into a duct or louvreVertically upwards, away from the roof
Typical useKitchens with filtration, booths, labsStandard kitchen hood exhaust

If your duct goes straight from the hood to the roof with few bends, an upblast fan is usually simpler and more economical. Read our upblast fan guide for the sizing steps, which apply to utility fans as well.

How to size a utility fan

  1. Airflow: start from the exhaust rate the hood needs (CFM). For an unlisted wall canopy, the International Mechanical Code uses 200 to 550 CFM per foot of hood depending on the cooking duty.
  2. Static pressure: add up the resistance of the hood filters, duct, bends and any ecology unit. Utility fans are usually chosen precisely because this number is high.
  3. Selection: choose the model whose fan curve delivers your airflow at that pressure, with a margin for filter loading over time.
  4. Drive: belt drive lets the speed be adjusted by changing the pulley ratio, which is useful when the system is balanced on site.

CBA utility fan sizes and specifications

ModelSizeAirflow (CFM)Airflow (m³/h)Motor
CBA8Size 83,000≈ 5,1000.75 HP
CBA10Size 103,500≈ 5,9501 HP
CBA14Size 144,800≈ 8,1601.5 HP
CBA16Size 166,000≈ 10,1902 HP
CBA18 (2 HP)Size 187,000≈ 11,8902 HP
CBA18 (5.5 HP)Size 189,000≈ 15,2905.5 HP
CBA20 (2 HP)Size 208,500≈ 14,4402 HP
CBA20 (4 HP)Size 2010,000≈ 16,9904 HP
CBA24Size 2412,000≈ 20,3905.5 HP
Nominal catalogue values. Actual airflow depends on the static pressure of your duct system.

Sizes 18 and 20 come with two motor options. The higher-power versions (size 18 at 5.5 HP and size 20 at 4 HP) move more air and keep their performance better against high resistance, such as an ecology unit with fully loaded filters.

Construction data

ModelCasing thickness (mm)Weight without motor (kg)Maximum speed (rpm)
CBA81.5553,000
CBA101.5652,900
CBA142752,400
CBA162852,100
CBA1821001,700
CBA202.51051,500
CBA242.51451,250
From the manufacturer’s catalogue.

Installation and maintenance tips

  • Install the fan on a rigid base with anti-vibration mounts, and use flexible connectors between the fan and the duct. The fan must not carry the weight of the duct: support the ductwork on its own frame.
  • Leave access to the belt guard, bearings and motor for maintenance.
  • Check belt tension, bearing condition and fan wheel cleanliness at each service visit.
  • If the system includes an ecology unit, follow its filter cleaning and replacement schedule; blocked filters reduce the airflow of any fan.
  • Coordinate the exhaust system with your ANSUL R-102 fire suppression system as the design requires.

Common problems

What you noticePossible causes (manufacturer’s catalogue)
The fan does not turnWrong voltage, power off or wrong wiring, overload protection tripped, blown fuse, loose pulley or failed belt
Too little airWrong direction of rotation, static pressure higher than designed, restricted or blocked inlet or outlet
Too much airStatic pressure lower than designed, or the fan is not installed in the right position
Unusual noise or strong vibrationSwitch the fan off and repair the fault before using it again

Before the first start, check the fan for transport damage, make sure nothing blocks the wheel or the duct, and confirm that the fan turns in the marked direction.

Frequently asked questions

Do I need a utility fan if I install an ecology unit?

In most cases, yes. The filters in an ecology unit add resistance that a roof fan may not overcome, so a utility fan is the usual choice. We size the fan together with the ecology unit.

Can a utility fan be installed indoors?

Yes. Utility fans can be installed on the roof, at ground level or in a plant room, provided the outlet is ducted to the outside and there is access for maintenance.

What is the difference between the 2 HP and 5.5 HP size 18 models?

The 2 HP model moves 7,000 CFM and the 5.5 HP model 9,000 CFM (nominal). The 5.5 HP version is for systems with higher airflow needs or higher resistance.

Do you supply utility fans across Saudi Arabia?

Yes. We are based in Makkah and supply customers across the Kingdom, including Jeddah and Riyadh.

Get a recommendation

Call or WhatsApp us on 0571535353, email info@amh-co.com or use our contact page. Send us the hood size, duct route and any filtration you plan to use, and we will recommend the right model.

Share:

Request a Quote

Tell us a little about your business and what you need. Our team will send you a formal quotation within one business day.

اطلب عرض سعر

أخبرنا عن نشاطك وما تحتاجه، وسيرسل لك فريقنا عرض سعر رسمي خلال يوم عمل واحد.