Ecology Unit Guide: Smoke and Odour Control for Commercial Kitchens

An ecology unit is a filtration unit installed in a commercial kitchen exhaust duct to remove grease, smoke and cooking odours before the air leaves the building. This guide explains how ecology units work, when a kitchen needs one, how to choose and install the right size, and how to maintain it. It is based on the manufacturer’s operation manual for the HEL-4000, HEL-8000 and HEL-12000 electrostatic precipitators and our product data, and is written by the AMH-CO team, who supply and install ecology units, kitchen exhaust fans and ANSUL fire suppression systems in Saudi Arabia.

When does a kitchen need an ecology unit?

  • Restaurants in malls, towers and mixed-use buildings, where the exhaust cannot be discharged high above the roof and could reach offices, homes or air intakes.
  • Kitchens close to neighbours, where smoke and food smells lead to complaints.
  • Grills, charcoal and wok cooking, which produce heavy smoke and strong odours.
  • Projects where the building owner or the authorities require smoke and odour control on kitchen exhaust.

How an ecology unit cleans the air

Our HEL ecology units are electrostatic precipitators (ESP). They treat the exhaust in stages:

  1. Mesh filter: a washable aluminium mesh filter removes most of the larger oil, smoke and grease particles.
  2. Ioniser: a high-voltage section gives even very fine particles (down to about 0.01 micron) an electric charge.
  3. Collector plates: the charged particles are attracted to the aluminium collector plates and stick to them. The collected grease drains down into an oil sump, and clean air leaves the unit.
  4. Odour treatment: the collector cell produces a small amount of ozone that helps break down odours. Models with UV-C lamps (254 nm) add photolysis, which breaks down odour compounds more effectively.
  5. Activated carbon filter (optional): for full odour control, a separate carbon filter (our CF series) is added after the unit, matched to the same airflow.

Removal efficiency depends on the airflow. The less air passes through the unit compared with its rating, the higher the efficiency. At its full rated airflow a single unit removes about 90–93% of the cooking fume (manufacturer’s manual); with lower airflow it reaches up to about 95% in a single pass, and up to 99% with two units in series. For example, a unit rated for about 7,000 CFM that handles a 4,000 CFM exhaust works at the higher end, while the same unit at 7,000 CFM works at 90–93%. The units have an automatic intensity control that keeps the removal rate high as the plates get dirty, door-open power-off protection, protection against over-current, over-voltage, over-temperature, arcing and short circuits, and terminals for a building management system (BMS).

Choosing the right size

Choose the ecology unit by the airflow of the exhaust system: the manual requires the system airflow to stay within the unit’s rated airflow, and a unit with some spare capacity works at a higher efficiency. Units can be stacked vertically or horizontally, side by side to handle more air, or one after the other to raise the removal rate.

Ecology unitAirflow (m³/h)Airflow (CFM)Electrostatic cellsPower (with UV / without)Matching carbon filter
HEL-40003,500 – 4,0002,060 – 2,3501180 W / 100 WCF-4000
HEL-80007,000 – 8,0004,118 – 4,7062500 W / 200 WCF-8000
HEL-1200010,000 – 12,0005,882 – 7,0593900 W / 300 WCF-12000
Power supply 220–240 V AC. Static pressure of the HEL unit about 39 Pa; carbon filters about 200 Pa (product data).

Example: a hood served by a size 16 upblast fan (about 5,800 CFM nominal) needs more than a HEL-8000. In that case a HEL-12000 is the right size, or the system is redesigned around a fan and unit with matching airflow.

The activated carbon filter (CF series)

The electrostatic stage removes particles, but cooking odours are gases. The activated carbon filter removes them, and according to the manufacturer’s catalogue it has these features:

  • Activated carbon granules with a nominal pore size as small as 0.4 nanometres, which adsorb odours and gas and vapour contaminants.
  • It also adsorbs excess ozone from UV-C lamps, so pairing it with a UV ecology unit helps stop ozone from being released outside.
  • It is installed between the ecology unit and the exhaust fan: hood → ecology unit → carbon filter → exhaust fan.
  • Hard, rigid granules with a low pressure drop that suit high humidity, held in perforated galvanized trays that are easy to replace.
  • Modular design: units can be connected together for higher airflow.
Carbon filterAirflow (m³/h)Airflow (CFM)Carbon traysResistanceGross weight
CF-40003,500 – 4,0002,060 – 2,3504200 Pa55 kg
CF-80007,000 – 8,0004,118 – 4,7068200 Pa90 kg
CF-1200010,000 – 12,0005,882 – 7,05912200 Pa120 kg
Manufacturer’s catalogue: carbon steel cabinet 1.2 mm (18 gauge), 4 mm pellets, iodine value 550 mg/g, carbon life 3–5 months.

Installation requirements

  • Install the unit level, so the grease drains into the oil sump instead of being pulled into the exhaust fan.
  • Keep at least 650 mm of free space in front of the access door for maintenance. A ceiling-mounted unit needs a maintenance platform in front of it.
  • Give the duct before the unit a straight run of at least 2.5 times the duct diameter, and use bends with a centre-line radius of 1.5 times the diameter. Where this is not possible, a deflector is needed, otherwise the removal rate drops.
  • Support the ductwork separately: its weight must not rest on the unit.
  • Do not install the unit too close to the hood. Steam or flames from the cooking line can short-circuit the cells, and fire entering the unit can damage the electronics. The manufacturer’s layout shows a fire damper between the hood and the unit.
  • Install it in the correct airflow direction (the direction can be reversed on site), connect a proper earth, and keep the working temperature between −10 and 60°C. The cabinet can be installed outdoors.

The ecology unit and your exhaust fan

Every filtration stage adds resistance that the exhaust fan must overcome. According to the product data, the HEL unit adds about 39 Pa and the activated carbon filter about 200 Pa, on top of the hood filters, the ductwork and the bends. A roof fan that worked well before the unit was added may no longer move enough air.

That is why kitchens with an ecology unit usually use a utility (centrifugal) fan, which is designed for higher resistance. In the manufacturer’s layout the unit sits between the hood and the exhaust fan, so the fan handles air that has already been cleaned. We size the fan and the ecology unit together.

Fire protection

An ecology unit is part of the exhaust duct system, and grease collects inside it. The ANSUL R-102 system design manual includes specific nozzle arrangements for protecting electrostatic precipitators in the exhaust system, so the fire suppression design must take the unit into account. Tell your ANSUL designer if an ecology unit is installed or planned. The manufacturer’s daily check also includes making sure the fume temperature at the unit does not exceed 70°C.

Maintenance

WhenWhat to do (manufacturer’s schedule)
Every dayKeep the area around the unit clean, check that the oil sump is not overflowing and empty it, check that the unit is switched on and the indicator lights are normal, and look for air leaks at the unit and ducting.
Every month (at least)Clean the collector cell and remove the oil inside the unit. Busy kitchens, grills and charcoal cooking need more frequent cleaning.
Activated carbon filterReplace the carbon every 3 to 5 months, depending on the amount of cooking (product data).

How the collector cell is cleaned

  1. Switch off and isolate the power, and hang a “Do not switch on” sign if the switch is away from the unit. There is high voltage inside.
  2. Wear protective glasses and gloves, because the cleaning solution is alkaline.
  3. Take out the collector cell and soak it for no more than 20 minutes in warm water (40–50°C) mixed with caustic soda at 1:20, in a stainless steel or plastic tank, lifting it up and down every 2 minutes.
  4. Rinse the cell and its insulators with a high-pressure water jet.
  5. Let the cell dry completely before putting it back. A wet cell can short-circuit; if needed, run the exhaust fan for about an hour to dry it.
  6. Refit the cell in the correct airflow direction, close the door and switch the unit back on. The green light shows that it is running.

Common problems

What you noticeLikely cause
Crackling sound and the green light is offDirty or wet collector cell, metal debris, bent ioniser blades or plates, or the cell is too close to the hood
Red light on, green light offFaulty power switch or high-voltage power supply
Smoke or smell still coming outDirty collector cell and mesh filter, arcing in the cell, a power supply fault or a leak in the ductwork
From the troubleshooting table in the manufacturer’s manual.

Frequently asked questions

How efficient is an ecology unit?

It depends on the airflow. At its full rated airflow a single unit removes about 90–93% of the cooking fume; with less air than its rating it reaches up to about 95%, and two units in series up to 99%.

What is the difference between an ecology unit and a carbon filter?

The ecology unit (HEL) uses electrostatic cells to remove grease and smoke particles. The activated carbon filter (CF) removes odours and gases. Kitchens that need full odour control use both, with the same airflow rating.

Which ecology unit size do I need?

Match the unit to the airflow of your exhaust system: HEL-4000 for up to 4,000 m³/h, HEL-8000 for up to 8,000 m³/h and HEL-12000 for up to 12,000 m³/h. Larger systems use several stacked units.

How often should the ecology unit be cleaned?

The manufacturer’s schedule is daily checks and cleaning the collector cell at least once a month. Heavy cooking needs more frequent cleaning.

Do I need a stronger exhaust fan with an ecology unit?

Often yes. The unit and especially the carbon filter add resistance, so a utility (centrifugal) fan is usually the right choice. We check the fan and the unit together.

Can the ecology unit be installed outdoors?

Yes. According to the manufacturer, the powder-coated cabinet can be installed outdoors without a shelter, with 650 mm of maintenance space in front of the door.

Does the ecology unit affect the ANSUL system?

Yes. The unit is part of the exhaust duct system, and the R-102 design manual has specific protection for electrostatic precipitators, so the fire suppression design must include it.