Fresh Air Fan Guide: How Much Make-Up Air Does a Kitchen Need?

A fresh air fan (also called a make-up air or supply fan) brings outside air into a commercial kitchen to replace the air that the exhaust fan removes. This guide explains why a kitchen needs make-up air, how much it needs, how to size and place the fan, and how it works with the exhaust system and the fire suppression system. It is written by the AMH-CO team, who supply and install fresh air fans, exhaust fans and ANSUL fire suppression systems in Saudi Arabia.

Why a kitchen needs make-up air

Every cubic metre of air the hood exhausts must be replaced from somewhere. Without a supply fan, the air is pulled in through doors, windows and gaps, and the kitchen is under strong negative pressure. The signs are familiar:

  • Doors are hard to open or slam shut, and there is a whistling draft at the doors.
  • The hood stops capturing smoke properly, even with a powerful exhaust fan.
  • Gas burners and pilot flames flicker or burn poorly, and flue gases may be pulled back into the room.
  • Dust, heat and insects are pulled in from outside, and the kitchen gets hotter.

How much fresh air do you need?

Start from the airflow of your exhaust fan. A common design practice is to supply about 80 to 90% of the exhausted air with the fresh air fan, and the fan manufacturer’s catalogue recommends 80%. The kitchen then stays slightly negative compared with the dining area, so cooking smells do not spread into the restaurant, while the hood still has enough replacement air to work properly. The remaining air comes in from the dining area or adjoining spaces.

Example: a kitchen exhausting 3,500 CFM through a size 10 utility fan needs roughly 2,800 to 3,150 CFM of make-up air. A size 12 fresh air fan (3,600 CFM nominal) covers this with room for the loss through the intake filter and supply ducts.

Fresh air fan sizes and specifications

Fresh air fanSizeAirflow (CFM)Airflow (m³/h)Motor
Size 10Size 102,100≈ 3,5701 HP
Size 12Size 123,600≈ 6,1201.5 HP
Size 15Size 154,700≈ 7,9902 HP
Size 18 – 2 HPSize 185,450≈ 9,2602 HP
Size 18 – 5 HPSize 188,400≈ 14,2705 HP
Nominal catalogue values. Actual airflow depends on the filter and the resistance of the supply ductwork.

All models are roof-mounted filtered supply units with a fully welded housing in galvanized or stainless steel and a direct connection to standard circular ducting. According to the manufacturer’s catalogue, the fan uses a double-inlet, forward-curved centrifugal impeller that is laser-cut and balanced to grade G4.0 of ISO 1940, the drive cover opens by hand for cleaning, and the motors run on 220 V single-phase or 380 V three-phase, 60 Hz. Size 18 comes in two versions: 2 HP (5,450 CFM) and 5 HP (8,400 CFM) for large kitchens.

Where to place the fan and the supply air

  • Keep the intake away from the exhaust outlet. Following NFPA guidance, the fan catalogue puts the supply fan intake at least 3 m from all exhaust fans; where that is not possible, the vertical separation between exhaust and supply must be at least 914 mm. Codes such as the International Mechanical Code set similar limits, so the kitchen does not breathe its own smoke back in.
  • Filter the intake. In Saudi conditions the intake filter keeps sand and dust out of the kitchen and out of the ductwork.
  • Do not blow air across the hood. Supply diffusers that blow fast air towards the front of the hood disturb the smoke plume and pull it out of the hood. Spread the air at low speed, away from the hood edges.
  • Balance the system after installation. Check that doors open normally and that the hood captures smoke at full cooking load.

Make-up air and fire suppression

According to the ANSUL R-102 manual, make-up or supply air fans that are built into the protected hood must shut down when the fire suppression system operates, while the exhaust fan may keep running to help carry the agent through the duct. Tell your fire suppression designer how the fresh air fan is wired, so the shutdown can be included in the design.

Maintenance

  • Check and clean the intake filter regularly, and more often during dusty and sandstorm seasons. A blocked filter cuts the airflow and puts the kitchen back under negative pressure.
  • Inspect the fan, motor and impeller at each service visit, and make sure the impeller turns freely and is clean.
  • Check that the roof curb and the intake hood are weather-tight.
  • Switch the fan off before any maintenance. The catalogue recommends cleaning the fan at least once a year, without a high-pressure washer or strong solvents. The sealed bearings need no routine maintenance.
  • Whenever the exhaust system changes (a new hood, a bigger exhaust fan, or an ecology unit), check that the fresh air fan still supplies enough air.

Frequently asked questions

Do I need a fresh air fan if my kitchen has windows?

Usually yes. Open windows and doors do not provide a controlled, filtered air supply, and in Saudi summers they let in heat and dust. A fresh air fan supplies a known amount of filtered air where it is needed.

How big should the fresh air fan be?

As a common design practice, about 80 to 90% of the exhaust airflow. For example, a 3,500 CFM exhaust needs roughly 2,800 to 3,150 CFM of make-up air.

Why is the kitchen kept slightly negative?

So that cooking smells and smoke stay in the kitchen and do not spread into the dining area or the rest of the building.

Does the fresh air fan stop when the fire suppression system operates?

Make-up air fans built into the protected hood must shut down when the ANSUL system operates, according to the R-102 manual. The design should include this interlock.

Which sizes do you supply?

Sizes 10, 12, 15 and 18, from 2,100 to 8,400 CFM, with motors from 1 to 5 HP.

Get a recommendation

Call or WhatsApp us on 0571535353, email info@amh-co.com or use our contact page. Tell us the size of your exhaust fan and the kitchen layout, and we will recommend a matching fresh air fan.

Share:

Request a Quote

Tell us a little about your business and what you need. Our team will send you a formal quotation within one business day.

اطلب عرض سعر

أخبرنا عن نشاطك وما تحتاجه، وسيرسل لك فريقنا عرض سعر رسمي خلال يوم عمل واحد.